- 5 Channel 4-20mA Analog Output
- Supports 2 x 10/100Base-T(X) ports
- Supports Full/Half-Duplex, auto MDI/MDI-X on each port
- Supports 1 x RS232 and 1 x RS485 Serial Connection up to 921600 Baud
- Embedded web interface for ease of use
- Instant switch between Server-Client Operating Modes with buttons
- Up to 10 client connection in Server Mode
- DHCP Server Capability
- Easy to follow Device Status on web interface
- Device Address changeable via web interface
- Modbus TCP to RTU Gateway functionality for Modbus packages with different addresses (Different than device own address)
- Output configuration can be defined by user for restart
- Output values can be saved and applied during auto restart
- I/O Mirror functionality: Device can duplicate output from a Modbus input device
- Easy to follow Device Parameters such as Device Up Time, Modbus read counter etc. on web interface
- Easy to follow Serial and Ethernet data packages on web interface
- Black List and White List based IP Filter in TCP Server Mode
- Firmware Upgrade over Web
- 2 firmware storage capability on same device (1 active only)
- 5-48V DC wide range power input (allows up to 60 V DC)
- Wide operating temperature range from -40 to 85 °C
- Rugged Metal IP-40 housing design
- DIN-Rail mounting
TECHNOLOGY
ETHERNET SWITCH TECHNOLOGY
Ethernet Standards
IEEE 802.3 for 10Base-T
IEEE 802.3u for 100Base-T(X)
IEEE 802.3x Flow Control
Mac Table
1K MAC address entry
Processing
Store-and-Forward
Memory
448K bits packet buffer memory
MODBUS CHARACTERISTICS
Protocol
Modbus TCP
Modbus Address
Default value is 0x01
Changeable via Web Interface
Modbus TCP to RTU Gateway Functionality
Modbus TCP packages with different addresses (Different than device own address) converted to Modbus RTU and sent to Serial interface and serial packages received are sent to Ethernet side after converting to Modbus TCP
Save Output Values Before Auto Restart
Default enabled and when system auto restarts the values are saved and applied after restart
Changeable via Web Interface
Save Output Values and Apply on Power Up
Default disabled, user can activate and enter parameters for each output individually
Changeable via Web Interface
I/O Mirror Functionality
Default disabled
If enabled, device can read input value of remote HUR device and duplicate those values as output
Monitoring Parameters
Modbus Read counter
Time counter (in seconds)
FW version
Device Up Time
Serial and TCP packages
CONNECTORS AND PORTS
Console Port
Micro USB connection for LOG in 115200 baud
10/100T(X) RJ45 Ports
Ethernet Connection on 2 ports
Serial Ports
5 pin wired Terminal Connection
Tx, Rx, GND for RS232
A and B for RS485
Reset Buttons
Reset to Client and Reset to Server Operating modes buttons
INPUT CONNECTORS AND INDICATORS
I/O ConnectorsTerminal Connectors
Analog Outputs: Polarity is important.
5 Analog Outputs total 10 connection pins.
4-20mA Analog Output designed for 24V 250ohm load or 12V 125ohm load.
Over Voltage Protection
LED INDICATORS
Power Indicator
Power LED
10/100T(X) Indicators
Activity LEDs:
ETH1, ETH2 and CKL (Activity of device itself)
System Indicators
Status LED,
Tx and Rx of data LEDs and Server LED
(LED ON: Server Operating Mode, LED OFF: Client Operating Mode)
Console Indicators
Tx and Rx of data LEDs
POWER
Input Range
100 - 240V AC (120 – 370V DC), 50Hz to 60Hz AC input
Isolation
Fully Isolated >4200Vrms, 5mA 1 Min
Insulation: Class II
PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS
Enclosure
Metal, IP 40
Dimensions
43 x 95 x 124 (w x d x h) mm
Weight
~400gr
Storage Temperature
-40 to 105 °C
Operating Temperature
-30 to 70 °C
Operating Humidity
5% to 95%Non-condensing
HUR695: 5 Channel 4-20mA Analog Output Modbus TCP Remote IO Device, 2x 10/100 T(x) ETH ports, 1 x RS232 & 1 x RS485, 100 - 240V AC (120 – 370V DC), 50Hz to 60Hz AC Power Input