- 8 Channel 5-275V AC-DC, 100mA Digital Optocoupler Output
- Device Address changeable with Modbus RTU commands
- Easy to Monitor Device Parameters such as Device Up Time, Modbus RTU read counter etc. with Modbus Commands
- Supports Modbus RTU Protocol over RS485 with 115200 8N1 Data Type
- Easy to Use Test and Parameter Change Software
- Easy Firmware Upgrade over Serial Line
- Output Values can be saved and Applied After Auto Restart
- Output Configuration for device power up can be defined by user with Modbus Commands
- 100 - 240V AC (120 – 370V DC), 50Hz to 60Hz AC wide range power input
- Wide operating temperature range from -25 to 70 °C
- Rugged Metal IP-40 housing design
- DIN-Rail mounting
MODBUS RTU DETAILS - HUR OUTPUT MODELS
Protocol
Modbus RTU
115200 8N1
Modbus RTU Address
Default value is 0x01
Changeable via Modbus Command
Save Output Values Before Auto Restart
Default is enabled and when system auto resets (every 24 hour) the values are saved and applied after restart
Changeable via Modbus Command
Save Output Values and Apply on Power Up
Default is disabled, user can activate and enter parameters for each output individually
Changeable via Modbus Command
Monitoring Parameters
Modbus RTU Read counter
Time counter (in seconds)
FW version
I/O TERMINAL AND INDICATORS - 1 Slot x 8 Channel Digital Optocoupler Output
I/O ConnectorsTerminal Connectors
Digital Outputs: 1
Slot x 8 Channel Output terminals polarity is not importantTotal 16 connection pins for each slot.
5-275V AC-DC, 100mA Digital Optocoupler Outputs
Isolation
Digital Optocoupler Output:
3750 Vrms for 1 min
Over Voltage Protection
Digital Optocoupler Output: 275V
Non-repetitive peak on-state pulse current: 80A
Output Status LEDs
Shows which pin is ON and OFF for Digital Output versions for each slot.
INTERFACE, INDICATORS AND FIMRWARE UPGRADE
RS485 Terminal
Terminal Connector for 2 wire RS485 connection and GND.
Activity LEDs
Tx LED: Flashes when the device sends Modbus RTU packages
Rx LED: Flashes when the device receives Modbus RTU packages
System LED
Flashes during normal operation
Firmware Upgrade over Serial Line
Available over RS485 Serial Line
POWER - AC
Input Range
100 - 240V AC (120 – 370V DC), 50Hz to 60Hz Wide Range AC Power Input
Isolation
Fully Isolated >4200Vrms, 5mA 1 Min
Insulation
Class II
PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS - AC POWERED MODELS
Enclosure
Metal, IP 40
Dimensions
43 x 95 x 124 (w x d x h) mm
Weight
~400gr
Storage Temperature
-40 to 105 °C
Operating Temperature
-25 to 70 °C
Operating Humidity
5% to 95% Non-condensing
HUR218: 8 Channel 5-275V AC-DC, 100mA Digital Optocoupler Output Modbus RTU Remote I/O Device, 1 x RS485, 90 - 265V AC (100 – 370V DC), 47Hz to 63Hz AC Power Input