- 4 Slots x 8 Channel 12-275V AC-DC, 60mA Digital Optocoupler Input
- Supports 2 x 10/100Base-T(X) ports
- Supports Full/Half-Duplex, auto MDI/MDI-X on each port
- Embedded web interface for ease of use
- Instant switch between Server-Client Operating Modes with buttons
- Up to 10 client connection in Server Mode
- DHCP Server Capability
- Easy to follow Device Status on web interface
- Device Address changeable via web interface
- Easy to follow Device Parameters such as Device Up Time, Modbus read counter etc. on web interface
- Easy to follow Serial and Ethernet data packages on web interface
- Black List and White List based IP Filter in TCP Server Mode
- Firmware Upgrade over Web
- 2 firmware storage capability on same device (1 active only)
- 100 - 240V AC (120 – 370V DC), 50Hz to 60Hz AC wide range power input
- Wide operating temperature range from -30 to 70 °C
- Rugged Metal IP-40 housing design
- DIN-Rail mounting
TECHNOLOGY
ETHERNET SWITCH TECHNOLOGY
Ethernet Standards
IEEE 802.3 for 10Base-T
IEEE 802.3u for 100Base-T(X)
IEEE 802.3x Flow Control
Mac Table
1K MAC address entry
Processing
Store-and-Forward
Memory
448K bits packet buffer memory
MODBUS CHARACTERISTICS
Protocol
Modbus TCP
Modbus Address
Default value is 0x01
Changeable via Web Interface
Monitoring Parameters
Modbus Read counter
Time counter (in seconds)
FW version
Device Up Time
TCP packages
CONNECTORS AND PORTS
Console Port
USB Type C or Micro USB connection for LOG in 115200 baud
10/100T(X) RJ45 Ports
Ethernet Connection on 2 ports
Reset Buttons
Reset to Client and Reset to Server Operating modes buttons
INPUT CONNECTORS AND INDICATORS
I/O ConnectorsTerminal Connectors
Digital Inputs: 4 Slots x 8 Channel 12-275V AC-DC, 60mA Digital Optocoupler Input
8 Channel Input terminals and polarity is not important. 2 pins for each connection and total 16 connection pins for each slot.
12-275 AC-DC, 60mA Digital Optocoupler Inputs.
Isolation
Digital Optocoupler Input:
4470Vrms 1min
Over Voltage Protection
Digital Optocoupler Input:
275V
LED INDICATORS
Power Indicator
Power LED
10/100T(X) Indicators
Activity LEDs:
ETH1, ETH2 and HUR (Activity of device itself)
System Indicators
Status LED,
Tx and Rx of data LEDs and Server LED
(LED ON: Server Operating Mode, LED OFF: Client Operating Mode)
Slot LEDs
S-1, S-2, S-3 and S-4: Turns On for 1 second and Turns OFF for 1 second under normal operation of I/O Interface.
Each LED corresponds to related I/O Slot.
Console Indicators
Tx and Rx of data LEDs
POWER
Input Range
100 - 240V AC (120 – 370V DC), 50Hz to 60Hz AC input
Isolation
Fully Isolated >4200Vrms, 5mA 1 Min
Insulation: Class II
PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS
Enclosure
Metal, IP 40
Dimensions
115 x 970 x 126 (w x d x h) mm
Weight
~700gr
Storage Temperature
-40 to 105 °C
Operating Temperature
-30 to 70 °C
Operating Humidity
5% to 95%Non-condensing
HUR813: Multi Slot, 4 x 8 Channel 12-275V AC-DC, 60mA Digital Optocoupler Input Modbus TCP Remote IO Device, 2x 10/100 T(x) ETH ports, 100 - 240V AC (120 – 370V DC), 50Hz to 60Hz AC Power Input