- Reads electricity meters with IEC 62056-21 (mode C, with automatic mode A and B detection; mode D selectable) and maps the values to a predefined Modbus register table
- Reads the meter on its RS232 port (3-wire: Tx, Rx, GND)
- Meter data is verified: with the factory setting a reading is accepted only from a telegram with a correct checksum, and meter-side parity errors are counted
- Tells a missing reading from a value of zero: row validity mask and per-meter health, read over Modbus
- Built-in meter trace (diagnostic text on the modem line), switched on over Modbus, and standard Modbus exception replies
- Built-in write lock for the settings, the table and the firmware update commands, switched on over Modbus (factory setting: off)
- Values as 32-bit integers (FC03) and as float64 with the decimal point applied (FC04)
- Configurable Modbus address, reading period, meter count and meter addresses (number or text of up to 16 characters) via Modbus commands
- Built-in table of 64 OBIS rows; the table can be replaced by a user-defined table over Modbus
- Wide range power input: 7 - 24 V DC
- Wide operating temperature range from -40 to 85 C
- Very small form factor, only 2.1 x 4.2 x 4.4 cm
- ZTerminal for Windows: configuration and monitoring software
- Firmware upgradable over the serial line
CONNECTIONS AND PROTOCOLS - LKM114
| Modem Side Connection
| Meter Side Connection | Meter Side Protocol |
| LKM114 | RS485
| RS232 | IEC 62056-21 |
MODBUS DETAILS - LKM RTU Models
Modbus RTU Address
Default value is 0x01
Changeable via Modbus Command
Reading Period on Meter Side
Default value is 10 (in seconds), setting 5 to 254
Changeable via Modbus Command
IEC 62056-21 Protocol Table Id (ACK character)
Default value is 0x30 = ‘0’in ASCII
Changeable via Modbus Command
IEC 62056-21 Protocol Meter Reading Method
Verifies the whole telegram (checksum) and updates the registers from a correct telegram (factory setting); line-by-line reading can be selected
IEC 62056-21 Protocol Meter Read Out Data (built-in table of 64 rows)
Active and reactive energy with tariff rows (import and export, four tariffs)
Maximum demands (active, reactive, apparent, import and export)
Averages of active, reactive and apparent power, current, voltage, power factor and frequency
Manufacturer-specific rows
Other rows by the user table
Extendable by a user-defined OBIS table or by custom firmware
Monitoring Parameters
Readout counter
Time counter (in seconds)
per-meter health (read counters, age of the last reading, lost-meter flags)
row validity mask
meter trace
Query via Modbus Commands
RS232 TERMINAL
RS232 Connector
Terminal Connector for 3 wire RS232 connection Tx-Rx-GND
RS485 TERMINAL
RS485 Connector
Terminal Connector for 2 wire RS485 connection A - B and GND can be used as well.
INTERFACE AND INDICATORS
Operation Mode Selection SwitchSelects the operating mode of the device
Mode Selection
| Modem Side Communication Parameters
| Meter Side Communication Parameters
|
Mode 1 (LED 1 ON)
| 19200 8N1
| Starts with 300 baud rate and changes during transmission to target baud rate based on IEC62056-21 protocol
|
Mode 2 (LED 2 ON)
| 9600 8N1
| Starts with 300 baud rate and changes during transmission to target baud rate based on IEC62056-21 protocol
|
Mode 3 (LED 3 ON)
| 19200 8N1
| 19200 7E1 Fixed
|
Mode 4 (LED 4 ON)
| 9600 8N1
| 9600 7E1 Fixed |
LED IndicatorsFollowing LEDs available to show system status.
1 – Mode 1 LED
2 – Mode 2 LED
3 – Mode 3 LED
4 – Mode 4 LED
5 – System LED: Blinks every second
6 – Tx LED: Sending data from Modem Side to Meter Side
7 – Rx LED: Receiving data from Meter Side to Modem Side
Firmware Upgrade
Upgrade over the serial line of the modem side (e.g. RS232 on LKM111 or RS485 on LKM144). New-series units are updated over Modbus at the running speed: the image is verified before it is activated and an interrupted update leaves the old firmware running. Units with the original bootloader are updated at 19200 8N1 after a power cycle.
POWER - LKM DC Models
Power Input
7 - 24 V DC
(LKM124 can also get power directly from P1 Standard Interface)
Reverse Polarity Protection
Available
Thermal Shutdown Protection
Available
PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS - LKM DC POWERED MODELS
Enclosure
ABS, IP40
Dimensions
21 x 42 x 44 (h x w x d) mm
Weight
~60gr
Storage Temperature
-55 to 125 °C
Operating Temperature
-40 to 85 °C
Operating Humidity
5 % to 95 % non-condensing
ESD
Tested to EN IEC 61326-1; ESD 4 kV contact, 8 kV air
LKM114: Electricity Meter Protocol to Modbus RTU Protocol Gateway, Modem Side RS485 and Meter Side RS232, 7 - 24 V DC Power Input