- Especially plug and play designed for EMH LXQJ-XC meters
- Direct replacement for Variomod XC modules for EMH meters
- Auto reads EMH Electricity meters that communicates in IEC62056-21 standard and maps in predefined MODBUS register table
- Configurable Modbus address via Modbus Commands
- Configurable Reading Period on IEC6056-21 side via Modbus Commands
- Configurable Reading Table Number on IEC6056-21 side via Modbus Commands
- Gets power directly from meter
- Serial interface directly connected to meter ( with 15kV ESD protection)
- Wide operating temperature range from -40 to 85 °C
- Customization of reading process and register tables based on client request
- Firmware upgradable over serial line
CONNECTIONS AND PROTOCOLS - LKM614
| Modem Side Connection
| Modem Side Connection | Meter Side Protocol |
LKM614 | RS485 | Meter Own Interface (Directly connects to Meter) | IEC62056-21 |
MODBUS DETAILS - LKM RTU Models
Modbus RTU Address
Default value is 0x01
Changeable via Modbus Command
Reading Period on Meter Side
Default value is 10 (in seconds)
Changeable via Modbus Command
IEC62056-21 Protocol Meter Read Out Table
Default value is 0x30 = ‘0’in ASCII
Changeable via Modbus Command
IEC62056-21 Protocol Meter Reading Method
Reads each line of table and register data during reading
IEC62056-21 Protocol Meter Read Out Data
Date
Time
Import and Export Active Energy
Import and Export Reactive Energy
Reactive Energy in 4 Quadrants
Import and Export Maximum Demands
Active Power
Phase Currents for each phase
Phase Voltages for each phase
Frequency
Error Code
Extendable/Changeable via firmware change
Monitoring Parameters
IEC Read counter
Time counter (in seconds)
FW version
Query via Modbus Commands
RS485 TERMINAL
RS485 Connector
Terminal Connector for 2 wire RS485 connection A - B and GND can be used as well.
INTERFACE AND INDICATORS
Operation Mode Selection SwitchSelects the operating mode of the device
Mode Selection
| Modem Side Communication Parameters
| Meter Side Communication Parameters
|
Mode 1 (LED 1 ON)
| 19200 8N1
| Starts with 300 baud rate and changes during transmission to target baud rate based on IEC62056-21 protocol
|
Mode 2 (LED 2 ON)
| 9600 8N1
| Starts with 300 baud rate and changes during transmission to target baud rate based on IEC62056-21 protocol
|
Mode 3 (LED 3 ON)
| 19200 8N1
| 19200 7E1 Fixed
|
Mode 4 (LED 4 ON)
| 9600 8N1
| 9600 7E1 Fixed |
LED IndicatorsFollowing LEDs available to show system status.
1 – Mode 1 LED
2 – Mode 2 LED
3 – Mode 3 LED
4 – Mode 4 LED
5 – System LED: Blinks every second
6 – Tx LED: Sending data from Modem Side to Meter Side
7 – Rx LED: Receiving data from Meter Side to Modem Side
Firmware Upgarde
Upgrade over Serial Line
Available from Modem side Serial Line
Ex:RS232 on LKM111 or RS485 on LKM144
Device must be on operating mode 19200 8N1 for firmware upgrade process.
POWER - LKM DIRECT CONNECTED Models
Gets power directly from Meter
PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS - LKM DIRECT CONNECTED MODELS
Enclosure
ABS, IP51
Dimensions
105 x 45 x 27 (h x w x d) mm
Weight
~60gr
Storage Temperature
-55 to 125 °C
Operating Temperature
-40 to 85 °C
Operating Humidity
5% to 95%Non-condensing
LKM614: Electricity Meter Protocol to Modbus RTU Protocol Gateway, Modem Side RS485 and Meter Side is Direct Connection to Meter, Powered from Meter Interface