MODBUS RTU to P1 Companion Protocol Meter Gateway With RS485 2 Wire Connection on Modem Side and P1 Interface on Meter Side
LKM124
MODBUS RTU to P1 Companion Protocol Meter Gateway With RS485 2 Wire Connection on Modem Side and P1 Interface on Meter Side
per one
199.50 USD 210 USD
If you buy less than 5 items you will lose your 5% discount
-    Auto reads Electricity meters that communicates in P1 Companion Standard and maps in predefined MODBUS register table
-    Configurable Modbus address via Modbus Commands
-    Configurable Reading Period on P1 Companion Standard side via Modbus Commands
-    Auto request data from meter
-    Wide range power input: 5V – 24V DC
-    Wide operating temperature range from -40 to 85 °C
-    Very Small form factor, only 2.1 x 4.2 x 4.4cm
-    Customization of reading process and register tables based on client request
-    Firmware upgradable over serial line

MODBUS RTU AND P1 COMPANION STANDARD CHARACTERISTICS
Modbus RTU Address
Default value is 0x01
Changeable via Modbus Command
Reading Period on P1 Protocol Meter Side
Default value is 10 (in seconds)
Changeable via Modbus Command
P1 Protocol Meter Reading Method
Read each line of table and register data during reading
P1 Protocol Meter Read Out Data
Date
Time
Import and Export Active Energy
Import and Export Reactive Energy
Reactive Energy in 4 Quadrants
Import and Export Maximum Demands
Active Power
Phase Currents for each phase
Phase Voltages for each phase
Frequency
Error Code
Extendable/Changeable via firmware change and depends on meter data
Monitoring Parameters
IEC Read counter
Time counter (in seconds)
FW version
Query able via Modbus Commands


INTERFACE AND INDICATORS
P1 Connector
Terminal Connector for 3 wire P1 connection ( Data, Data Request, GND) on Meter Side
RJ12 cable connection to meter must be prepared for meter connection based on desired length.
Check manual for cable pins.
RS485 Connector
Terminal Connector for 2 wire RS485 connection and GND on Modem Side
Operation Mode Selection Switch
Selects the operating mode of the device.
( can be different depending on customer specific firmware)



Mode Selection
Modem Side Communication Parameters
Meter Side Communication Parameters
Mode 1 (LED 1 ON)9600 8N1
9600 8N1 Fixed
Mode 2 (LED 2 ON)
19200 8N1
19200 8N1 Fixed
Mode 3 (LED 3 ON)
57600 8N1
57600 8N1  Fixed
Mode 4 (LED 4 ON)
115200 8N1
115200  8N1  Fixed
LED Indicators
Following LEDs available to show system status.
1 – Mode 1 LED
2 – Mode 2 LED
3 – Mode 3 LED
4 – Mode 4 LED
5 – System LED: Blinks every second
6 – Tx LED: Sending data from Modem Side to Meter Side
7 – Rx LED: Receiving data from Meter Side to Modem Side


FIRMWARE UPGRADE
Upgrade over Serial Line
Available from Modem side Serial Line
RS485 on LKM124


Device must be on operating mode 19200 8N1 for firmware upgrade process.


POWER
Power Input
5V – 24V DC
Reverse Polarity Protection
Available
Thermal Shutdown Protection
Available


PHYSICAL AND ENVIRONMENTAL CHARACTERISTICS
Enclosure
ABS, IP40
Dimensions
21 x 42 x 44 (h x w x d) mm
Weight
~60gr
Storage Temperature
-55 to 125 °C
Operating Temperature
-40 to 85 °C 
Operating Humidity
5% to 95%Non-condensing


LKM124: Modem side RS485, Meter side P1 Interface, Modbus RTU to P1 Companion Standard Meter gateway

LKM Series Electricity Meter Protocol to Modbus Protocol Gateways with MQTT (and LoRaWAN)
LKM Series Electricity Meter Protocol to Modbus Protocol Gateways with MQTT (and LoRaWAN)
STG Series WMBus (Wireless MBus) - Modbus Protocol Gateway with MQTT
STG Series WMBus (Wireless MBus) - Modbus Protocol Gateway with MQTT
TLM Series LoRa Modems and LoRaWAN EndNode Modems
TLM Series LoRa Modems and LoRaWAN EndNode Modems
CKL Series Modbus TCP and RTU Gateways and Serial to Ethernet Gateways
CKL Series Modbus TCP and RTU Gateways and Serial to Ethernet Gateways
BSB Series Industrial Unmanaged Ethernet Switch (with Broadband Power Line)
BSB Series Industrial Unmanaged Ethernet Switch (with Broadband Power Line)
KMK Series Optical Probes for Energy Meters
HUR Series Modbus TCP and RTU Remote I/O Devices with MQTT (and LoRaWAN)
BKV Series USB Tools, RS232/485 Converters, Ethernet Switches, USB 2.0 Hubs, 868MHZ WMBus Converters, P1 Meter Converters
BKV Series USB Tools, RS232/485 Converters, Ethernet Switches, USB 2.0 Hubs, 868MHZ WMBus Converters, P1 Meter Converters
BKV Series USB Tools, RS232/485 Converters, Ethernet Switches, USB 2.0 Hubs, 868MHZ WMBus Converters, P1 Meter Converters
MBC Series IEC62056-21 Protocol Auto Baud Changer
KMK Series Optical Probes for Energy Meters
REDZ Software Solutions